On October 9, 2026, FERC accepted and PJM Interconnection, L.L.C.’s (PJM) proposed definition of “Large Load” and Large Load Registry under the PJM tariff, but otherwise rejected PJM’s proposed Interim Resource Adequacy Service (IRAS) and related Bring Your Own New Capacity (BYONC) frameworks.  Specifically, FERC rejected PJM’s IRAS and BYONC proposals because they either appeared to be outside of FERC’s jurisdiction or had not been shown to be just and reasonable and not unduly discriminatory or preferential.  Commissioner David Rosner concurred in a separate statement.

Among the various proposals, PJM proposed to define Large Load as an end-use customer’s or customers’ load with a cumulative peak load of at least 50 MW at a single electrical site behind one or more points of interconnection, with certain additional qualifications set forth in the definition.  PJM further proposed to establish additional new defined terms “New Large Load” and “Eligible New Large Load,” along with a Large Load Registry and a new IRAS framework, under which Load Serving Entities (LSEs) that seek to use Network Integration Transmission Service (NITS) to serve New Large Loads must either designate new capacity resources covering the New Large Load’s peak load or have that load be subject to curtailment during capacity shortfall conditions.  PJM also proposed rules for BYONC arrangements and, beginning with the 2029/2030 Delivery Year, rules to exclude Eligible New Large Load from PJM’s Variable Resource Requirement curve. 

FERC accepted PJM’s proposed Large Load definition, finding that PJM’s proposed 50 MW threshold for loads to qualify as Large Loads strikes a just and reasonable balance between capturing the larger loads into which PJM needs visibility to ensure the reliability of its system and excluding smaller loads that do not raise the same reliability concerns in PJM.  FERC also found that PJM’s proposed Large Load Registry will enable PJM to better forecast load growth, plan and manage its transmission system, and address the operational impacts of Large Loads on the PJM transmission system.

FERC rejected the remainder of PJM’s proposal as an integrated package.  Although PJM’s transmittal letter described IRAS as placing obligations only on Electric Distributors, FERC found, among other things, that the proposed tariff language appeared to go beyond FERC’s authority by placing obligations directly on retail customers.  FERC also found, inter alia, that PJM had not offered sufficiently detailed evidence concerning how (i) PJM’s treatment of Electric Distributors and LSEs taking NITS differently in the resource adequacy context based on the characteristics of their retail customers and (ii) PJM’s proposal to lock in BYONC capacity accreditation are just and reasonable and not unduly discriminatory or preferential.  FERC directed PJM to submit within 30 days a compliance filing with only the Large Load definition and Large Load Registry.  FERC also offered PJM guidance should it choose to refile.

FERC Commissioner David Rosner concurred in a separate statement to emphasize that, if PJM refiles its proposal, it must justify curtailing IRAS load on a mandatory basis before curtailing load that has voluntarily enrolled in a demand response program.

FERC’s order, issued in Docket No. ER26-3515-000, can be found here.